THIS DRAWING SHOWS ONE
VERSION OF THE ENVIROSAFE PUMP DRAIN INSERT INSTALLED IN A TYPICAL CARBON STEEL REDUCER
PUMP DRAIN. THIS VERSION IS INSTALLED FLUSH WITH THE TOP OF THE REDUCER AND IS
TAPERED TO ALLOW FOR MORE VOLUME. THE PUMP DRAIN INSERT PROVIDES CONTINUOUS FLOW
WHILE MAINTAINING A WATER SEAL THAT PREVENTS HYDROCARBONS FROM ESCAPING TO THE ATMOSPHERE,
THEREBY COMPLYING WITH EPA AIR QUALITY REGULATIONS RESTRICTING EMISSIONS OF VOC'S SUCH AS
BENZENE. DRAIN LINES SHOULD BE PIPED INTO THE DRAIN SO AS TO ALLOW FOR REMOVAL OF
THE CAP FOR FLUSHING TO REMOVE ANY HYDROCARBONS FLOATING ON THE WATER SEAL. A
MINIMUM WATER SEAL DEPTH OF 6" IS RECOMMENDED TO PREVENT BACK PRESSURE FROM FORCING
ANY HYDROCARBON VAPORS THROUGH THE WATER SEAL ONCE THE SEWER SYSTEM HAS BEEN SEALED.
THE PUMP DRAIN INSERT CAN PREVENT SEWER EXPLOSIONS BY ELIMINATING CONTACT OF SEWER
GASES WITH AN IGNITION SOURCE.![]() |
| COVERED BY U.S. PATENT NO.'S 4,682,907; 4,776,722; 5,028,320; 5,062,735 |